LT AERIAL BUNDLED CONDUCTOR (ABC) POLYMERIC INSULATED AS PER BS 7879 ( PT - 5 ) 1999

Nomianl Cross Sectional Area of conductor sqmm

Maximum Conductor D.C Resistance at 20 Deg.C Ohm/Km

Minimum Average Thickness of XLPE Insulation
mm

Ultimate Tensile strength of conductor
KN

25

1.20

1.3

4.1

35

0.868

1.3

5.6

50

0.641

1.5

7.6

70

0.443

1.5

11

95

0.320

1.7

15.3

120

0.253

1.7

19.4

DESIGNATION

CONDUCTOR

Average Thickness of Insulating Sheath Specified Value
(mm)

Core
 

Breaking Strength

Outside Diameter

Type

Nomianl Cross Sectional Area of sqmm

Number of Strands

Maximumm Linear Resistance at 20 Deg.C
Ohm/Km

Minimum Conductor Diameter (mm)

Minimum (daN)

Maximum
(daN)

Minimum

Maximum

Phase

16

7

1.91

4.7

190

290

1.2

7

7.9

Or

25

7

1.20

6.0

300

450

1.4

8.7

9.6

Neutral 

35

7

0.868

7.0

420

630

1.6

10.1

11.1

 Non

50

7

0.641

8.2

600

900

1.6

11.3

12.3

Return

70

12

0.443

9.8

840

1260

1.8

13.3

14.3

Neutral Return 

54.6

7

0.63

9.2

1660

-

1.6

12.3

13.0

 

In HT Aerial Bunched Cables the phase Conductor Consists of Stranded Circular Compacted Aluminium Conductor. Conductor Screened with extruded S.G Compound, Insulated with Cross linked Polythylene (XLPE) Insulation Screened with Extruded S.C Compound followed by Copper tape or Plastic coated aluminium tape, outer sheathed with PVC or Black weather resistant Polyethylene and three such phase conductor are twisted around bare stranded circular compacted aluminium alloy messenger conductor which takes all the mechanical stress & also serve as the earth cum neutral conductor.

 

DESIGNATION

COMPLETE BUNCHED CABLES>

Approx. Overall DIA
mm

Approx. Total Mass
KG/Km

6.35/11KV 3 x 35 + 70

53

1450

6.35/11KV 3 x 70 + 70

59

1900

The first part refers to phase conductor and second to bare messenger conductor.

   1  2  3  

 Home | Company Profile | Products | Clients | Technical Parameters | Quality Assurance | Feedback | Contact Us