THERMOCUPLE
|
EXTENSION
OR COMPENSATING CABLE
|
NOMINAL
ANALYSIS OF THE ALLOYS
|
BRITISH
SPECIFICATION BS 4937 AND AMERICAN SPECIFICATION ANSI
MC 96-1
|
|
mV
|
TEMP.
|
TOLERANCE
|
|
STANDARD
|
SPECIAL
|
T1-T2
(Type K) |
T1-T2
(KX) |
T1:90%
Ni-10% Cr
T2:95% Ni-Al-Mn-Si |
4.095
8.4137 |
100°
C
200° C |
±2.2°
C
0 to 200° C |
-
- |
T1-T2
(Type K) |
Cu
(VX) |
Cu:100%
Cu
V:44% Ni Bal Cu |
4.095
- |
100°
C
- |
±2.2°
C
0 to 100° C |
-
- |
T1-T2
(Type K) |
Fe-410
Alloys
(WX) |
Fe:100%
Fe
410:43% Ni-2% Mn-2% Fe Bal Cu |
-
- |
-
- |
-
- |
-
- |
T1-T2
(Type E) |
T1-E
(EX) |
T1:90%
Ni-10% Cr
E:44% Ni Bal Cu |
6.317
13.419 |
100°
C
200° C |
±1.7°
C
0 to 200° C |
-
- |
Cu-T
(Type T) |
Cu-T
(TX) |
Cu:100%
Cu
T:44% Ni Bal Cu |
-2.152
4.277 |
-60°
C
+100 ° C |
±1°
C
-60 to +100° C |
±0.5°
C
-60 to100° C |
Fe-J
(Type J) |
Fe-J
(JX) |
Fe:100%
Fe
J:44% Ni Bal Cu |
5.268
10.777 |
100°
C
200° C |
±2.2°
C
0 to 200° C |
±1.1°
C
0 to 200° C |
Pt-Pt
Rh 10 or 13%
(Type S R) |
Cu-11
Alloys
(SX) |
Cu:100%
Cu
11:3% Ni-2% Mn Bal Cu |
0.645
1.440 |
100°
C
200° C |
±0.057°
Cmv(5° C)
0 to 200° C |
-
- |